{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7MN32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7MN32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, 3VA2216-7MN32-0JA0, 3-pole molded case circuit breaker (MCCB), motor protection version, 160 A rated continuous current, ETU350M electronic trip unit, shunt trip release, 330 kA breaking capacity at 240 V AC.","salesMarkdown":"## Motor protection MCCB with ETU350M trip unit Breaking capacity is rated at 330 kA at 240 V AC, 242 kA at 415 V AC and 440 V AC, 187 kA at 500 V AC, and 52.5 kA at 690 V AC. The integrated shunt trip release (STL) allows remote tripping from a safety circuit or emergency-stop chain. Above that, derating applies: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If the MCCB is mounted in a sealed enclosure or next to heat-generating components, use the 55 °C or 60 °C row as your design limit — the breaker will carry 160 A only if the air around it stays under 50 °C. The 105 mm width is standard for a 3-pole 160 A frame in the 3VA2 series — it occupies three 35 mm DIN module spaces. Depth of 86 mm leaves clearance behind the panel door for wiring and the shunt trip connections.","metaTitle":"Siemens 3VA2216-7MN32-0JA0 SENTRON MCCB, 160 A, 330 kA at 24","metaDescription":"Siemens 3VA2216-7MN32-0JA0 SENTRON molded case circuit breaker, 160 A rated current, 330 kA breaking capacity at 240 V AC. Motor protection version with ETU350M electronic trip uni","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2216-7MN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"55 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"2 400 A","Adjustable response value current / li min.":"2 400 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"2 400 A","Adjustable response value current / Isd min.":"480 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570056&mlfb=3VA2216-7MN32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-7MN32-0JA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"What is the breaking capacity of 3VA2216-7MN32-0JA0 at 415 V?","answer":"242 kA at 415 V AC, which is the same rating as at 440 V. At 240 V it reaches 330 kA, and at 690 V it drops to 52.5 kA."},{"question":"Does 3VA2216-7MN32-0JA0 include phase failure protection?","answer":"Yes, the ETU350M trip unit includes phase failure detection. A lost phase on the line side will trip the breaker before single-phasing damages the motor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7MN32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}