{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7MN32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7MN32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-7MN32-0JH0, molded case circuit breaker, 3-pole, 160 A, motor protection design, with shunt trip and auxiliary switches.","salesMarkdown":"## SENTRON 3VA2 MCCB for motor protection — 160 A, flat derating curve Three-pole construction, with a maximum interrupting rating of 330 kA at 240 V AC, stepping down to 242 kA at 415/440 V, 187 kA at 500 V, and 4.5 kA at 690 V — the SCCR curve lets you coordinate downstream without oversizing for the available fault current at your service voltage. The flat thermal curve up to 70 °C means you don't have to open the enclosure or add forced cooling when the panel runs hot; the breaker holds its full 160 A. Maximum power loss of 19.7 W is the heat the breaker dissipates at rated current — relevant for enclosure thermal calculations, especially in a multi-breaker lineup on a common bus. No undervoltage release fitted; if you need UVR, that's a different variant or an add-on module. ## Panel integration — dimensions and mounting The 3VA2 family mounts on a DIN rail or can be screw-mounted to a backplate; the 105 mm width (4.13 in) is a standard 3-pole MCCB footprint, so it drops into existing panel cutouts sized for similar-frame breakers.","metaTitle":"Siemens 3VA2216-7MN32-0JH0 SENTRON MCCB, 160 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2216-7MN32-0JH0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, motor protection design. 330 kA SCCR at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2216-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"45 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570058&mlfb=3VA2216-7MN32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth and width of 3VA2216-7MN32-0JH0?","answer":"Depth is 86 mm (3.39 in), width is 105 mm (4.13 in), height is 181 mm (7.13 in)."},{"question":"Will 3VA2216-7MN32-0JH0 drop into a panel specified for 3VA1110-5EF32-0AM0?","answer":"Both are 3-pole SENTRON MCCBs, but the 3VA2216 is a larger frame (160 A vs the 3VA1110's lower rating) and physically wider — verify the panel cutout and bus spacing before substitution."},{"question":"What compliance documentation does this brand provide?","answer":"Siemens SENTRON breakers typically carry UL, CSA, CE, and IEC certifications, with RoHS and REACH declarations available through the manufacturer's documentation portal. Specific certs for this order code should be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7MN32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}