{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-8JP42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-8JP42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-8JP42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-8JP42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-8JP42-0AA0, 4-pole molded case circuit breaker, 160 A rated continuous current, ETU550 electronic trip unit, 440 kA breaking capacity at 240 V AC, line protection version.","salesMarkdown":"The Siemens SENTRON 3VA2216-8JP42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current, carrying a 440 kA interrupting capacity at 240 V AC — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. Rated insulation voltage is 800 V, so it's comfortable in 480 V or 600 V class panels with headroom to spare. The 160 A rating holds flat across the full operating temperature range from 40 °C up to 70 °C — no derating curve to watch when the panel runs hot. The breaker measures 140 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA2 frame footprint. The breaker includes communication functionality, so it can report status and trip events to a higher-level control system without adding a separate module.","metaTitle":"Siemens 3VA2216-8JP42-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2216-8JP42-0AA0 molded case circuit breaker, 160 A rated, 4-pole, ETU550 electronic trip unit, 440 kA at 240 V. Current lifecycle stage, available to order. Requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","title":"3VA2216-8JP42-0AA0","Height":"181 mm","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"53 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [in]":"3.4 in","Width [in]":"5.5 in","Height [in]":"7.1 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class L Icu=150kA @ 415V 4-pole, line protection ETU550, LSI, In=160A overload protection Ir=63A...160A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In N conductor protection adjustable (OFF, up to 160%) nut keeper kit","Number of poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"adjustable OFF; 20% bis160%","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 920 A","Adjustable response value current / li min.":"240 A","Adjustable response value current / lr min.":"64 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"96 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"L","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=372538&mlfb=3VA2216-8JP42-0AA0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-8JP42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-8JP42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}