{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2220-5MN32-0AE0, 3-pole, 200 A rated, motor protection design, 187 kA breaking capacity at 240 V AC.","salesMarkdown":"## MCCB sized for motor protection duty Breaking capacity reaches 187 kA at 240 V, dropping to 121 kA at 415 V, 75.6 kA at 500 V, and 5.2 kA at 690 V — the high 240 V figure suits it for North American 277/480 V wye systems where the line-to-ground fault current can be severe on the secondary side of a 1500 kVA transformer. Dimensions are 105 mm wide × 181 mm tall × 86 mm deep — a standard SENTRON 3VA2 frame size that drops into the same mounting footprint as other 200 A SENTRON MCCBs, so a panel designed for a 3VA2 frame accepts this unit without re-drilling the backplate. Maximum power loss of 46 W at rated load — factor that into enclosure ventilation calculations if the panel is sealed; a 200 A breaker dumping 46 W into a small steel box can raise internal ambient above the 70 °C operating limit. Comes with 4 HQ auxiliary switches pre-installed (design of the auxiliary switch: 4 auxiliary switches HQ), so there is no separate add-on order for status feedback to the PLC or alarm annunciator.","metaTitle":"Siemens 3VA2220-5MN32-0AE0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0AE0 molded case circuit breaker, 200 A rated, 3-pole, motor protection design, 187 kA at 240 V. Current lifecycle stage. Available to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570072&mlfb=3VA2220-5MN32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2220-5MN32-0AE0 include phase failure protection?","answer":"Yes, phase failure detection is built into the motor protection design — it will trip on a lost phase to prevent single-phase motor damage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}