{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0AF0, molded case circuit breaker, 3-pole, 200 A rated continuous current, motor protection version with ETU350M electronic release, breaking capacity 187 kA at 240 V AC.","salesMarkdown":"Rated continuous current Iu is 200 A at 40 °C, and it holds that rating through 50 °C; above that it derates to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — figures that cover most industrial distribution panels with high fault current. Max power loss is 75 W; plan ventilation accordingly if the enclosure is tightly packed.","metaTitle":"Siemens 3VA2220-5MN32-0AF0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2220-5MN32-0AF0 SENTRON molded case circuit breaker, 200 A rated at 40 °C, 3-pole, motor protection with ETU350M release. Breaking capacity 187 kA at 240 V. Active produ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-5MN32-0AF0","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"192 A","at 60 °C":"188 A","at 65 °C":"184 A","at 70 °C":"180 A","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, motor protection ETU350M, LSI, In=200A overload protection Ir=80A...200A short-circuit protection Isd=3...15 x Ir, Ii=15 x In nut keeper kit 1 auxiliary switch HQ 1 trip alarm switch HQ","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"200 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"75 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"200 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"80 A","Adjustable response value current / Isd max.":"3 000 A","Adjustable response value current / Isd min.":"600 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570073&mlfb=3VA2220-5MN32-0AF0"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2220-5MN32-0AF0 at 415 V?","answer":"121 kA at 415 V AC, which also applies at 440 V. At 240 V it is 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 17 kA."},{"question":"Where can I buy 3VA2220-5MN32-0AF0 and how is it quoted?","answer":"This MCCB is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the rated continuous current of this MCCB?","answer":"Rated continuous current Iu is 200 A at 40 °C, and it holds 200 A through 50 °C. Above that it derates: 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}