{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0BL0, molded case circuit breaker (MCCB), 3-pole, 200 A, interrupting capacity 187 kA at 240 V, motor protection design, undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2220-5MN32-0BL0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current of 200 A across its full ambient temperature range from 40 °C to 70 °C — no derating needed up to the enclosure's thermal limit, which simplifies panel layout when the breaker sits near other heat sources. Interrupting capacity is the number that decides whether this breaker clears a fault or welds shut: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V. Designed for motor protection — meaning the trip curve is shaped to handle motor inrush without nuisance tripping, and it includes phase failure detection so a single-phased motor draws current on the remaining legs until the breaker opens. The undervoltage release (UVR) lets a safety PLC or E-stop chain drop the breaker when control voltage is lost, which is standard for guarded machine cells. Maximum power loss is 46 W at rated current. In a sealed, non-ventilated enclosure that heat must be factored into the thermal budget; a 200 A breaker pulling 46 W is typical for this frame size, but grouping several breakers in a small cabinet may require forced air or a larger enclosure.","metaTitle":"Siemens 3VA2220-5MN32-0BL0 SENTRON MCCB, 200 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0BL0 molded case circuit breaker, 200 A, 3-pole, 187 kA at 240 V. Motor protection design with undervoltage release. Current lifecycle. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570080&mlfb=3VA2220-5MN32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2220-5MN32-0BL0 and what is the price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time; submit an RFQ for a firm quote."},{"question":"What is the interrupting capacity of this MCCB at 415 V?","answer":"121 kA at 415 V, and the same 121 kA at 440 V."},{"question":"Does 3VA2220-5MN32-0BL0 include phase failure protection?","answer":"Yes, it includes phase failure detection as part of the motor protection design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}