{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, molded case circuit breaker (MCCB), 3VA2220-5MN32-0CC0, 3-pole, 200 A, motor protection design, undervoltage release, 2 HQ auxiliary switches, phase failure detection.","salesMarkdown":"That 200 A holds the motor branch under full load without nuisance tripping, provided the thermal memory is respected on re-acceleration after a fault. Short-circuit breaking capacity follows the voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V. The trip time band sits between 4 s and 15 s, which is the window the thermal bimetal needs to clear a sustained overload before the magnetic element takes over on a hard short. The basic switch variant is 3VA2220-5MN32-0AA0, so this -0CC0 order code adds the UVR and aux switches at the factory rather than field-fitting them. The 105 mm width is the same as other 3VA2 frame-size breakers, so a panel laid out for a 160 A or 250 A sibling accepts this 200 A unit without re-drilling the backplate. Maximum power loss is 46 W; account for that in the enclosure thermal calculation if the panel is sealed. ## Environmental limits and storage","metaTitle":"Siemens 3VA2220-5MN32-0CC0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2220-5MN32-0CC0 SENTRON molded case circuit breaker, 200 A rated at 40-70 °C, 3-pole motor protection with UVR and phase failure detection. Active production. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570082&mlfb=3VA2220-5MN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2220-5MN32-0CC0 and what is the lead time?","answer":"This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time; submit an RFQ for the latest lead-time estimate."},{"question":"Will 3VA2220-5MN32-0CC0 drop into a panel specified for 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON MCCBs in the 3VA2 frame family, so the mounting footprint and busbar pitch are the same. The -0CC0 carries a 200 A rating versus the 160 A of the -5JP32 variant, so the busbar and cable sizing must be verified for the higher current — the physical fit is identical."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"Siemens typically supplies IEC/EN 60947-2 compliance, CE marking, and UKCA for this SENTRON series. RoHS and REACH declarations are available through the standard documentation package. Specific UL listing should be confirmed per the exact variant — the evidence does not list UL directly for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}