{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2220-5MN32-0HA0, 200 A continuous, 3-pole, motor protection design, shunt trip release, 187 kA at 240 V.","salesMarkdown":"Rated short-circuit breaking capacity (Icu) hits 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 5.2 kA at 690 V. Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — a standard 3-pole MCCB footprint for a 200 A frame. Bolts into a panel or mounts on a mounting plate; no DIN-rail clip on this frame size. The 86 mm depth includes the rear arc chamber, so leave clearance behind the panel for the exhaust vents.","metaTitle":"Siemens 3VA2220-5MN32-0HA0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2220-5MN32-0HA0 SENTRON molded case circuit breaker, 200 A at 40-70°C, 3-pole, motor protection design with shunt trip. Breaking capacity 187 kA at 240 V. Active product","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570089&mlfb=3VA2220-5MN32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2220-5MN32-0HA0 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number."},{"question":"What is the continuous current rating of this MCCB?","answer":"200 A continuous, and it holds that rating from 40 °C to 70 °C ambient with no derating — useful for warm enclosures."},{"question":"Does this breaker include a shunt trip?","answer":"Yes, it has a shunt trip release (STL) for remote opening. No undervoltage release or ground-fault monitoring."},{"question":"What are the physical dimensions of 3VA2220-5MN32-0HA0?","answer":"105 mm wide, 181 mm tall, 86 mm deep — standard 3-pole 200 A frame size."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}