{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0HH0, molded case circuit breaker, motor protection design, 200 A, 3-pole, with phase failure detection, shunt trip, and auxiliary switches.","salesMarkdown":"## Siemens SENTRON 3VA2220-5MN32-0HH0 — Motor Protection MCCB Interrupting capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V — the steep drop at 690 V means this breaker is best applied on 400 V class systems where its full fault-clearing capability is available. The width is the critical panel cutout dimension; verify busbar and adjacent device spacing against the 105 mm pole pitch. Maximum power dissipation is 46 W, which should be factored into enclosure thermal calculations, particularly in sealed or high-ambient cabinets. For BOM freeze or qualification projects, the manufacturer's change-control process applies; documented compliance (RoHS, REACH, UL, IEC) is part of the SENTRON series standard documentation package.","metaTitle":"Siemens 3VA2220-5MN32-0HH0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2220-5MN32-0HH0 SENTRON molded case circuit breaker, 200 A rated current, 3-pole, motor protection design with phase failure detection. Active lifecycle. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570091&mlfb=3VA2220-5MN32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2220-5MN32-0HH0?","answer":"Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA2220-5MN32-0HH0's interrupting capacity at 415 V?","answer":"The interrupting capacity at 415 V is 121 kA."},{"question":"Does 3VA2220-5MN32-0HH0 include phase failure detection?","answer":"Yes, phase failure detection is built into this breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}