{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0JA0, molded case circuit breaker, 3-pole, 200 A rated continuous current, motor protection version with electronic ETU350M release, shunt trip, interrupting capacity 187 kA at 240 V.","salesMarkdown":"It carries a shunt trip release integrated as standard. Interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 121 kA at 440 V, with 75.6 kA at 500 V and 17 kA at 690 V — enough for high-fault infrastructure panels where selectivity and SCCR headroom are non-negotiable. The 200 A rated continuous current (Iu) holds across the entire 40 °C to 50 °C band without derating — at 55 °C it drops to 192 A, at 60 °C to 188 A, at 65 °C to 184 A, and at 70 °C to 180 A. The ETU350M electronic release gives adjustable thermal-magnetic curves and phase-failure detection, so it can be coordinated downstream of a larger SENTRON or upstream of a motor starter. ## Panel Integration & Mounting The 3-pole 200 A frame uses the same cutout and bus-bar spacing as other SENTRON 3VA2 breakers, so swapping a 160 A unit for this 200 A version requires no panel rework — just verify the bus-bar ampacity and the upstream fault rating.","metaTitle":"Siemens 3VA2220-5MN32-0JA0 SENTRON MCCB, 200 A, 3P, Motor Pr","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0JA0 molded case circuit breaker, 200 A continuous, 3-pole motor protection with ETU350M release. 187 kA at 240 V. Active production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-5MN32-0JA0","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"192 A","at 60 °C":"188 A","at 65 °C":"184 A","at 70 °C":"180 A","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, motor protection ETU350M, LSI, In=200A overload protection Ir=80A...200A short-circuit protection Isd=3...15 x Ir, Ii=15 x In nut keeper kit shunt trip (STL) 110-127V DC, AC 50/60Hz","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"200 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"75 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"200 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"80 A","Adjustable response value current / Isd max.":"3 000 A","Adjustable response value current / Isd min.":"600 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570093&mlfb=3VA2220-5MN32-0JA0"},"ai":{"faq":[{"question":"Who supplies 3VA2220-5MN32-0JA0 and how is it quoted for volume purchases?","answer":"It is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of this MCCB at 415 V?","answer":"121 kA at 415 V, and the same rating holds at 440 V."},{"question":"What is the depth of 3VA2220-5MN32-0JA0?","answer":"86 mm depth, 105 mm width, 181 mm height."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}