{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2220-5MN32-0JC0, 200 A rated current at 40 °C, 3-pole, motor protection design, breaking capacity 187 kA at 240 V AC, 121 kA at 415 V AC, with shunt trip release and two auxiliary switches.","salesMarkdown":"## Motor protection MCCB with phase failure detection and shunt trip Breaking capacity is substantial: 187 kA at 240 V AC, 121 kA at 415 V AC and 440 V AC, tapering to 75.6 kA at 500 V AC and 5.2 kA at 690 V AC. That puts it in the high-interrupting category for industrial distribution — suitable for installations with high fault current potential, such as large motor control centers or transformer-fed switchboards. The basic switch variant is 3VA2220-5MN32-0AA0, so the -0JC0 suffix adds the shunt trip and auxiliary switch configuration. The 105 mm width is typical for a 200 A frame in the SENTRON range, so panel cutouts and busbar spacing designed for other 3VA2 breakers of similar rating will accept this unit without modification. ## Coordination and selectivity note The motor protection design means the thermal-magnetic or electronic trip curve is shaped for motor starting inrush — the minimum trip time is 4 s, maximum 15 s, which accommodates typical NEMA Design B or IEC motor start profiles. Phase failure detection adds an extra layer of protection against single-phasing, which is a common cause of motor winding failure.","metaTitle":"Siemens 3VA2220-5MN32-0JC0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0JC0 molded case circuit breaker, 200 A rated at 40 °C, 3-pole, motor protection design with phase failure detection. Breaking capacity 187 kA at 240","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570094&mlfb=3VA2220-5MN32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2220-5MN32-0JC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ with your quantity and target delivery window."},{"question":"What is the breaking capacity of 3VA2220-5MN32-0JC0 at 415 V?","answer":"121 kA at 415 V AC, and the same rating at 440 V AC. At 240 V it is 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 5.2 kA."},{"question":"Does 3VA2220-5MN32-0JC0 include a shunt trip?","answer":"Yes, it includes a shunt trip release (STL) and two HQ auxiliary switches as standard from the factory."},{"question":"What is the rated current of 3VA2220-5MN32-0JC0 at elevated temperatures?","answer":"200 A continuous from 40 °C through 70 °C — no derating required across that range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}