{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0JL0, molded case circuit breaker, 3-pole, 200 A, motor protection version, ETU350M electronic trip unit, 187 kA at 240 V.","salesMarkdown":"The Siemens 3VA2220-5MN32-0JL0 is a SENTRON molded case circuit breaker (MCCB) in a motor protection configuration, carrying a 200 A rated continuous current (Iu) across a 3-pole frame. That 200 A holds steady from 40 °C up to 50 °C, then derates to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C — so in a warm enclosure you still have headroom for a 180 A motor full-load amp draw without nuisance tripping. Breaking capacity is the other headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. That 187 kA at 240 V covers high-fault utility feeds; the 121 kA at 415 V handles most European industrial distribution. The 17 kA at 690 V is lower but still adequate for most 690 V motor circuits — just verify your available fault current at that voltage against the curve. The ETU350M electronic trip unit gives you phase-failure detection and a voltage-trigger function. The auxiliary contact block is loaded: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch. A shunt trip release (STL) is built in for remote opening. The base switch is 3VA2220-5MN32-0AA0, and the integrated auxiliary trip module is 3VA9688-0BL32. The 3VA2220-5MN32-0JL0 measures 105 mm wide, 181 mm high, and 86 mm deep. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.","metaTitle":"Siemens 3VA2220-5MN32-0JL0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0JL0 molded case circuit breaker, 200 A rated, 3-pole, motor protection with ETU350M trip unit. Breaking capacity 187 kA at 240 V. Active production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-5MN32-0JL0","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"192 A","at 60 °C":"188 A","at 65 °C":"184 A","at 70 °C":"180 A","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, motor protection ETU350M, LSI, In=200A overload protection Ir=80A...200A short-circuit protection Isd=3...15 x Ir, Ii=15 x In nut keeper kit shunt trip (STL) 110-127V DC, AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"200 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"75 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"200 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"80 A","Adjustable response value current / Isd max.":"3 000 A","Adjustable response value current / Isd min.":"600 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570096&mlfb=3VA2220-5MN32-0JL0"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2220-5MN32-0JL0 at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V (–). The 187 kA at 240 V covers high-fault utility feeds; the 121 kA at 415 V handles most European industrial distribution."},{"question":"Where can I buy 3VA2220-5MN32-0JL0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm offer."},{"question":"What trip unit does 3VA2220-5MN32-0JL0 use?","answer":"It uses the ETU350M electronic overcurrent release. That unit provides phase-failure detection and a voltage-trigger function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}