{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0KC0, molded case circuit breaker, 3-pole, 200 A rated at 40 °C, 187 kA interrupting capacity at 240 V, motor protection design with phase failure detection, shunt trip release, 2 auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2220-5MN32-0KC0 is a 3-pole molded case circuit breaker (MCCB) rated 200 A continuously from 40 °C up to 70 °C — no derating needed across that thermal band, which simplifies panel layout in warm enclosures. The interrupting capacity hits 187 kA at 240 V AC, 121 kA at 415/440 V, and 75.6 kA at 500 V — numbers that give selectivity headroom in high-fault distribution panels. Maximum power loss is 46 W, so factor that into thermal calculations for sealed enclosures.","metaTitle":"3VA2220-5MN32-0KC0 SENTRON MCCB, 200A, 3-Pole, 187kA at 240V","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0KC0 molded case circuit breaker, 200A, 3-pole, 187kA interrupting at 240V. Motor protection design with phase failure detection. Active production. S","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570098&mlfb=3VA2220-5MN32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2220-5MN32-0KC0 at 240 V?","answer":"187 kA at 240 V AC, with ratings also available at 415 V (121 kA), 440 V (121 kA), 500 V (75.6 kA), and 690 V (5.2 kA) (–)."},{"question":"Does 3VA2220-5MN32-0KC0 include phase failure detection?","answer":"Yes, phase failure detection is built into the motor protection design."},{"question":"What auxiliary switches and releases come with this MCCB?","answer":"It includes two auxiliary switches (HQ) and a shunt trip release (STL)."},{"question":"Where can I buy 3VA2220-5MN32-0KC0 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}