{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MN32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MN32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MN32-0KL0, Molded case circuit breaker, 3-pole, 200 A, 187 kA at 240 V, motor protection design, with shunt trip and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2220-5MN32-0KL0 is a 3-pole molded case circuit breaker rated for 200 A continuous at 40 °C, with a maximum breaking capacity of 187 kA at 240 V. The auxiliary switch configuration includes two auxiliary switches, one trip alarm switch, and one electrical alarm switch, giving the panel builder a full set of status signals without adding external blocks. The interrupting rating drops with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V. ## Current rating holds across the full temperature range That is unusual — most MCCBs start to derate above 40 °C. For a hot panel or a machine near a furnace, this means you do not have to oversize the frame to hold the load current. ## Motor protection design with integral phase failure detection The product design is explicitly for motor protection, and it includes phase failure detection as a standard function. That means it will trip on a lost phase without needing a separate phase-monitor relay — one less component to wire and troubleshoot on a motor branch circuit. ## Auxiliary and alarm switch complement The breaker ships with two auxiliary switches, one trip alarm switch, and one electrical alarm switch, plus a shunt trip release for remote opening. That is a full house of status contacts — enough to signal open/closed, trip, and alarm conditions to a PLC or annunciator without adding external switch modules.","metaTitle":"Siemens 3VA2220-5MN32-0KL0 SENTRON MCCB, 200A, 3-Pole, 187kA","metaDescription":"Siemens SENTRON 3VA2220-5MN32-0KL0 molded case circuit breaker, 200A rated, 3-pole, 187kA breaking at 240V. Motor protection design with phase failure detection. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570100&mlfb=3VA2220-5MN32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MN32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2220-5MN32-0KL0 at 240 V?","answer":"The breaker has a maximum breaking capacity of 187 kA at 240 V. At 415 V and 440 V it is 121 kA, at 500 V it is 75.6 kA, and at 690 V it is 5.2 kA."},{"question":"Does 3VA2220-5MN32-0KL0 include a shunt trip?","answer":"Yes, it includes a shunt trip release (STL) for remote tripping, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch."},{"question":"Where can I buy 3VA2220-5MN32-0KL0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MN32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MN32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}