{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MQ32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MQ32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MQ32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MQ32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-5MQ32-0AA0, Molded case circuit breaker, 3-pole, 200 A, motor protection, ETU860M trip unit, 187 kA at 240 V.","salesMarkdown":"The 3VA2220-5MQ32-0AA0: This is a Siemens SENTRON 3VA2 molded case circuit breaker, three-pole, rated 200 A continuous at 40 °C through 70 °C — meaning it holds full current across the whole panel ambient range, no derating curve to chase. It's built for motor protection, with an ETU860M electronic trip unit that gives you adjustable trip class (10A, 10/10E, 20/20E, 30), phase failure detection, ground-fault monitoring via summation current, and a communication function for remote status. The interrupting ratings are the real story here. At 240 V it clears 187 kA — that's a massive fault level, typical for a main or large feeder breaker in an industrial distribution panel. At 500 V it drops to 75.6 kA, and at 690 V it's 5.2 kA. The takeaway: this breaker is sized for high-fault upstream positions at 240–440 V, not for a 690 V motor branch. If your system is 480/277 V, the 75.6 kA at 500 V is the closest benchmark — confirm your available fault current against that figure. The 86 mm depth (3.39 in) means it clears most standard enclosure back-panels without hitting the door.","metaTitle":"Siemens 3VA2220-5MQ32-0AA0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2220-5MQ32-0AA0 molded case circuit breaker, 200 A rated, 3-pole, motor protection with ETU860M trip unit. Active production, sourced to order. Breaking capacity","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-5MQ32-0AA0","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, motor protection ETU860M, LSIG, In=200A overload protection Ir=80A...200A short-circuit protection Isd=1.2..15x In, Ii=3..15x In gr.-fault prot., can be sw. off Ig=0.2...1 x In, tg=0.05-0.8s nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Product version":"Motor protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Courant permanent assigné Iu":"200 A","design of I-trip / adjustable":"Yes","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10/10E, 20/ 20E, 30","Design Of The Overcurrent Release":"ETU860M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg max.":"200 A","Adjustable response value current / lg min.":"40 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"600 A","let-through energy characteristic / at 240 V":"DE_3VA2_2_200A_ETU_line u starter u motor_3u4p_240V","let-through energy characteristic / at 415 V":"DE_3VA2_2_200A_ETU_line u starter u motor_3u4p_415V","let-through energy characteristic / at 440 V":"DE_3VA2_2_200A_ETU_line u starter u motor_3u4p_440V","let-through energy characteristic / at 500 V":"DE_3VA2_2_200A_ETU_line u starter u motor_3u4p_500V","let-through energy characteristic / at 690 V":"DE_3VA2_2_200A_ETU_line u starter u motor_3u4p_690V","product feature / for G-tripping / adjustable":"Yes","product feature / for L-tripping / adjustable":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","set values setting current (Ii) / for I-tripping":"3-15;0","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Tripping Characteristic / Of The Lower Tolerance Band":"AK_3VA2_2_200A_ETU860M_MuC_uT","Tripping Characteristic / Of The Upper Tolerance Band":"AK_3VA2_2_200A_ETU860M_MuC_oT","reference value setting current (Ii) / for I-tripping":"x In","reference value setting current (InN) / for N-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","type of value list setting current (Ii) / for I-tripping":"St","type of value list setting current (InN) / for N-tripping":"St","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$640.08","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569079&mlfb=3VA2220-5MQ32-0AA0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MQ32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MQ32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}