{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-5MQ32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-5MQ32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-5MQ32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MQ32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 series, IEC frame 250, breaking capacity class M, Icu=55kA @ 415V, 3-pole, motor protection ETU860M, LSIG, In=200A.","salesMarkdown":"## Motor protection breaker with ETU860M LSIG trip unit The In rating is 200 A, with overload protection adjustable from 80 A to 200 A. Short-circuit protection Isd ranges 1.2–15× In, instantaneous Ii 3–15× In, and ground-fault Ig 0.2–1× In with a time delay tg of 0.05–0.8 s. Breaking capacity is Icu=55 kA at 415 V, class M. ## Integration notes The breaker ships with two auxiliary switch changeover contacts (H) and one trip alarm switch changeover, plus a nut keeper kit. Mounts in standard IEC switchgear panels; the ETU860M allows field-adjustable LSIG curves, making it suitable for motor control centers where selectivity and ground-fault coordination are required.","metaTitle":"Siemens 3VA2220-5MQ32-0AJ0 Circuit Breaker, 200A, 55kA @ 415","metaDescription":"Siemens 3VA2220-5MQ32-0AJ0 IEC frame 250 motor protection breaker, Icu=55kA @ 415V, 3-pole, ETU860M LSIG, In=200A. Active lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1508173&mlfb=3VA2220-5MQ32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-5MQ32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"What does the ETU860M LSIG trip unit protect against?","answer":"The ETU860M provides four protection functions: long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and ground-fault (G). The overload Ir is adjustable 80–200 A, short-time Isd 1.2–15× In, instantaneous Ii 3–15× In, and ground-fault Ig 0.2–1× In with a selectable time delay tg of 0.05–0.8 s."},{"question":"Where can I buy the 3VA2220-5MQ32-0AJ0?","answer":"This part is available to order through independent distribution. Submit an RFQ to confirm current pricing and lead time; the unit is quoted on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-5MQ32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-5MQ32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}