{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MN32-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MN32-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MN32-0BC0, molded case circuit breaker, motor protection, 3-pole, 200 A, interrupting rating 330 kA at 240 V, with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA2220-7MN32-0BC0 is a 3-pole molded case circuit breaker (MCCB) in the motor protection variant, rated for 200 A continuous current. It carries a punishing interrupting capacity — 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 5.2 kA at 690 V — so it can sit upstream of a motor branch or a distribution panel where fault currents are high. The 200 A rating holds flat from 40 °C up to 70 °C, meaning no derating headache in a warm enclosure. ## Integration dimensions and panel fit Physical footprint: 105 mm wide, 181 mm tall, 86 mm deep. That 86 mm depth (about 3.4 inches) is shallow enough for most 200 mm deep enclosures, but always check the handle throw and cable bending radius — the breaker itself fits, but the incoming lugs need clearance. The 3-pole block mounts via the standard MCCB footprint; no special adapter plate required. ## Electrical environment and compliance Rated insulation voltage is 800 V, so it's comfortable on 480/600 V systems with margin. Operating temperature spans -25 °C to 70 °C; storage range is -40 °C to 80 °C. The basic switch (the breaker mechanism without accessories) is order code 3VA2220-7MN32-0AA0, which is the core unit this UVR-equipped version builds on.","metaTitle":"Siemens 3VA2220-7MN32-0BC0 SENTRON MCCB, 200 A, 3-pole, 330","metaDescription":"Siemens SENTRON 3VA2220-7MN32-0BC0 molded case circuit breaker, 200 A continuous, 3-pole, interrupting up to 330 kA at 240 V. Motor protection version with undervoltage release and","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-7MN32-0BC0","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class C Icu=110kA @ 415V 3-pole, motor protection ETU350M, LSI, In=200A overload protection Ir=80A...200A short-circuit protection Isd=3...15 x Ir, Ii=15 x In nut keeper kit undervoltage release (UVR) 24V DC","Trip Indicator":"No","Number Of Poles":"3","Product version":"Motor protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2220-7MN32-0AA0","Courant permanent assigné Iu":"200 A","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational current of the frame size":"250 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570110&mlfb=3VA2220-7MN32-0BC0"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2220-7MN32-0BC0?","answer":"It is a 3-pole MCCB rated 200 A continuous, with interrupting capacity of 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 5.2 kA at 690 V. It includes an undervoltage release and phase failure detection."},{"question":"Where can I buy 3VA2220-7MN32-0BC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA2220-7MN32-0BC0 drop into a panel specified for 3VA2116-5HM42-0CC0 without rewiring?","answer":"No — the 3VA2220-7MN32-0BC0 is a 200 A, 3-pole motor protection MCCB with an undervoltage release and phase failure detection, while the 3VA2116-5HM42-0CC0 is a different rating and accessory configuration. Panel wiring and bus connections will differ; verify the physical footprint and terminal layout against your existing cutout and bus bars before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MN32-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}