{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MN32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MN32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MN32-0BL0, molded case circuit breaker, 3-pole, 200 A, 330 kA at 240 V, motor protection design, undervoltage release.","salesMarkdown":"## What this MCCB delivers The Siemens 3VA2220-7MN32-0BL0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 200 A continuously across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel schedules in warm enclosures. The motor protection design includes phase failure detection and a trip indicator, so a single-phasing event on a compressor or conveyor motor shows up visually on the breaker face. That means you get status feedback and a UVR without buying separate accessory kits or opening the breaker cover — a time saver on the panel build. The UVR drops the breaker if control voltage falls below its dropout threshold, which is standard for safety circuits that need to guarantee a power-off state when the control supply is lost. The base switch is order code 3VA2220-7MN32-0AA0, so if you ever need a bare breaker without auxiliaries, that is the core variant to cross-reference. The lifecycle stage for the 3VA2220-7MN32-0BL0 is listed as current — meaning Siemens still actively manufactures and supports this order code as a standard catalog item. No phase-out notice, no last-time-buy window. Maximum power loss is 46 W, so factor that into the enclosure thermal budget if the panel is sealed or has limited ventilation.","metaTitle":"Siemens 3VA2220-7MN32-0BL0 MCCB, 200A, 3-Pole, 330kA at 240V","metaDescription":"Siemens SENTRON 3VA2220-7MN32-0BL0 molded case circuit breaker, 200A rated, 3-pole, 330kA interrupting at 240V. Motor protection design with undervoltage release. Current lifecycle","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570112&mlfb=3VA2220-7MN32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2220-7MN32-0BL0?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ with your target quantity and delivery window; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2220-7MN32-0BL0's interrupting capacity at 415 V?","answer":"At 415 V the interrupting capacity is 242 kA. At 240 V it is 330 kA, and at 690 V it drops to 5.2 kA."},{"question":"Does 3VA2220-7MN32-0BL0 include an undervoltage release?","answer":"Yes, this variant is factory-fitted with an undervoltage release (UVR) that drops the breaker when control voltage is lost."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MN32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}