{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MN32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MN32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MN32-0CA0, molded case circuit breaker, 3-pole, 200 A, motor protection design, with undervoltage release, 86 mm depth.","salesMarkdown":"Three poles, 3VA frame. The breaking capacity hits 330 kA at 240 V and stays at 242 kA up to 440 V; at 690 V it drops to 5.2 kA — that's the voltage you watch for selectivity coordination on high-impedance systems. ## What's built in — and what isn't No auxiliary switch on board; no ground-fault monitoring version. It has no communication function and no voltage trigger. The trip indicator is absent, so fault diagnostics rely on the breaker's handle position or downstream monitoring. Phase failure detection is included, which matters for motor protection on unbalanced supplies. ## Panel fit — dimensions and environment Width 105 mm, height 181 mm, depth 86 mm. Drops into the standard SENTRON 3VA mounting footprint; no rewiring needed if replacing a same-frame 3VA2220 unit.","metaTitle":"Siemens 3VA2220-7MN32-0CA0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2220-7MN32-0CA0 SENTRON molded case circuit breaker, 200 A rated, 3-pole, motor protection design, 330 kA at 240 V. Current production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-7MN32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570113&mlfb=3VA2220-7MN32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"What is the 3VA2220-7MN32-0CA0 used for?","answer":"It is a molded case circuit breaker designed for motor protection, with phase failure detection and an undervoltage release, rated 200 A continuous at up to 70 °C ambient."},{"question":"Where can I buy the 3VA2220-7MN32-0CA0?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"Does the 3VA2220-7MN32-0CA0 include an undervoltage release?","answer":"Yes, the design of the auxiliary release is an undervoltage release (UVR), fitted as standard on this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MN32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}