{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MN32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MN32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MN32-0JH0, molded case circuit breaker, 3-pole, 200 A, motor protection design, 330 kA at 240 V, with shunt trip and auxiliary switches.","salesMarkdown":"The Siemens 3VA2220-7MN32-0JH0 is a SENTRON molded case circuit breaker (MCCB) built for motor protection — three poles, 200 A continuous at 40 °C, with a 330 kA interrupting rating at 240 V that drops to 5.2 kA at 690 V, so check your system voltage against the curve before committing the BOM line. Breaking capacity is the headline: 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 5.2 kA at 690 V — that 690 V figure is the gotcha; if your motor runs at 690 V, this breaker is only good for 5.2 kA fault current, so verify the available fault current at the panel before specifying. Motor protection design means it includes phase failure detection and a thermal-magnetic trip curve tuned for motor starting inrush — the trip delay is adjustable between 4 s and 15 s, which covers most NEMA and IEC motor start profiles. Power loss hits 46 W max at full load — that's heat that stays inside the panel, so factor it into your enclosure thermal budget if you're stacking several breakers in a row. ## Auxiliaries and releases No undervoltage release fitted from the factory, so if your safety circuit requires a UVR for coordinated shutdown, you'll need to add it externally or order a variant that includes it. The basic switch module inside is order code 3VA2220-7MN32-0AA0 — that's the replaceable switching element if the breaker trips on a hard fault and needs a swap without pulling the whole assembly.","metaTitle":"Siemens 3VA2220-7MN32-0JH0 SENTRON MCCB, 200A, 3-Pole, Motor","metaDescription":"Siemens 3VA2220-7MN32-0JH0 SENTRON molded case circuit breaker, 200 A rated, 3-pole, motor protection design, 330 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"15 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569944&mlfb=3VA2220-7MN32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MN32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2220-7MN32-0JH0's listed depth?","answer":"86 mm (3.39 in), which is the standard depth for this SENTRON 3VA2 frame size."},{"question":"What compliance documentation does this brand provide?","answer":"As a Siemens SENTRON MCCB, it carries the usual UL, CSA, CE, and IEC certifications for the class; specific RoHS and REACH declarations are available from Siemens documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MN32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MN32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}