{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MQ32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MQ32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MQ32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MQ32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MQ32-0BL0, molded case circuit breaker, 3-pole, motor protection design, 200 A rated at 40 °C, 330 kA interrupting at 240 V, 86 x 105 x 181 mm.","salesMarkdown":"The Siemens SENTRON 3VA2220-7MQ32-0BL0 is a 3-pole molded case circuit breaker (MCCB) designed specifically for motor protection, carrying a continuous current rating of 200 A across its full ambient temperature range from 40 °C to 70 °C — meaning no derating is needed for typical panel environments up to 70 °C ambient. Its interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V, and 187 kA at 500 V, but drops to 5.2 kA at 690 V; that high-end 690 V figure tells you this breaker is sized for 400 V class systems where fault current is the constraint, not a 690 V line where the available fault current is low. ## Motor protection features and panel integration This MCCB includes phase failure detection and an undervoltage release, tripping on a lost phase or sag below dropout threshold. The integrated communication function enables remote monitoring. A trip indicator is present. Maximum power loss is 46 W.","metaTitle":"Siemens 3VA2220-7MQ32-0BL0 SENTRON MCCB, 200 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2220-7MQ32-0BL0 molded case circuit breaker, 200 A rated at 40 °C, 3-pole, motor protection design, 330 kA at 240 V. Current lifecycle. Quoted to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2220-7MQ32-0BL0","Height":"181 mm","Maximum":"15 s","Minimum":"3 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class C Icu=110kA @ 415V 3-pole, motor protection ETU860M, LSIG, In=200A overload protection Ir=80A...200A short-circuit protection Isd=1.2...15 x In, Ii=15 x In gr.-fault prot., can be sw. off Ig=0.2...1 x In= tg=0.05-0.8s nut keeper kit undervoltage release (UVR) 24V DC 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Initial Value":"40 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"200 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"Yes","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"#BEZUG!","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10/10E, 20/ 20E, 30","Design Of The Overcurrent Release":"ETU860M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"37 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=643594&mlfb=3VA2220-7MQ32-0BL0"},"ai":{"faq":[{"question":"What is the depth of 3VA2220-7MQ32-0BL0?","answer":"The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MQ32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MQ32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}