{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MS32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MS32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MS32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MS32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MS32-0HH0, molded case circuit breaker, 3-pole, 200 A rated continuous current, starter protection version with ETU310M electronic trip unit, 330 kA breaking capacity at 240 V.","salesMarkdown":"The breaker carries a 330 kA interrupting rating at 240 V, scaling down to 242 kA at 415/440 V, 187 kA at 500 V, and 52.5 kA at 690 V — these figures govern its suitability for high-fault installations where upstream coordination demands full-rated SCCR headroom. The 200 A rating holds at 40 °C, 45 °C, and 50 °C without derating; above 50 °C it drops linearly to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C. The 86 mm depth, 105 mm width, and 181 mm height fit the standard SENTRON 3VA mounting footprint, compatible with the same busbar and lug kits used on the 3VA1 frame. ## Auxiliary and trip options The basic switch subassembly is order code 3VA2220-7MS32-0AA0, and the integrated auxiliary trip is 3VA9688-0BL30, both serviceable separately.","metaTitle":"Siemens 3VA2220-7MS32-0HH0 SENTRON MCCB, 200 A, 3-Pole, Star","metaDescription":"Siemens 3VA2220-7MS32-0HH0 SENTRON molded case circuit breaker, 200 A rated at 40 °C, 3-pole, 330 kA at 240 V. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"192 A","at 60 °C":"188 A","at 65 °C":"184 A","at 70 °C":"180 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"200 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2220-7MS32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU310M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"75 W","Reference code / acc. to DIN EN 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"0 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"600 A","Adjustable response value current / lr min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"I","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569972&mlfb=3VA2220-7MS32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MS32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2220-7MS32-0HH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is listed on this page."},{"question":"Will 3VA2220-7MS32-0HH0 drop into a panel specified for 3VA1110-5EE32-0JA0?","answer":"No, the 3VA2220 frame is physically larger (200 A class) than the 3VA1 frame, so it does not drop in without busbar and enclosure rework. The 3VA1110-5EE32-0JA0 is a lower-current MCCB and not a direct mechanical substitute."},{"question":"What are the key interrupting ratings for this breaker?","answer":"At 240 V the interrupting rating is 330 kA; at 415 V and 440 V it is 242 kA; at 500 V it is 187 kA; and at 690 V it is 52.5 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MS32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MS32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}