{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2220-7MS32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2220-7MS32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2220-7MS32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MS32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2220-7MS32-0JC0, molded case circuit breaker, 3-pole, 200 A rated, frame 600–3000 A, interrupting 330 kA at 240 V, 242 kA at 415 V, depth 86 mm, width 105 mm, height 181 mm.","salesMarkdown":"The Siemens SENTRON 3VA2220-7MS32-0JC0 is a 3-pole molded case circuit breaker (MCCB) with a fixed thermal-magnetic trip unit rated 200 A continuously across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The frame accepts trip units from 600 A up to 3000 A, meaning this breaker body can be re-fitted for a much larger load later, but as shipped it protects a 200 A circuit. Interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, and 187 kA at 500 V; at 690 V it drops to 5.2 kA, so confirm the available fault current at your system voltage before specifying. It is designed for starter protection — meaning it is sized to back up a motor starter rather than serve as the sole branch-circuit device on a resistive load. Verify the line and load lug spacing matches your existing bus stack — the 3VA2 family uses the same terminal pitch across the frame range.","metaTitle":"3VA2220-7MS32-0JC0 SENTRON MCCB, 200 A, 3-pole, 600–3000 A f","metaDescription":"Siemens SENTRON 3VA2220-7MS32-0JC0 molded case circuit breaker, 200 A rated, 3-pole, 600–3000 A frame, interrupting 330 kA at 240 V. Active production, sourced to order. Request qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"3 000 A","Minimum":"600 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.2 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"200 A","at 60 °C":"200 A","at 65 °C":"200 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Starter protection","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"46 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2220-7MS32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"200 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569975&mlfb=3VA2220-7MS32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2220-7MS32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2220-7MS32-0JC0?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; the part is sourced to order from Siemens distribution and quoted on request. No stock count or price is published here."},{"question":"What is the closest functional second-source to 3VA2220-7MS32-0JC0?","answer":"The closest functional peer is the 3VA2116-5HL32-0AK0 — same 3-pole frame, same interrupting ratings, same accessory suite, but rated 160 A instead of 200 A. It drops into the same panel cutout without rewiring."},{"question":"What are the key ratings of 3VA2220-7MS32-0JC0?","answer":"Rated continuous current 200 A (no derating from 40 °C to 70 °C). Frame accepts trip units from 600 A to 3000 A. Interrupting capacity 330 kA at 240 V, 242 kA at 415 V, 242 kA at 440 V, 187 kA at 500 V, 5.2 kA at 690 V. Three poles. Includes shunt trip and two auxiliary switches."},{"question":"Will 3VA2220-7MS32-0JC0 drop into a panel specified around 3VA2116-5HL32-0AK0?","answer":"Yes — both are 3-pole 3VA2 frame breakers with identical dimensions (105 mm wide, 181 mm high, 86 mm deep) and the same terminal pitch. No rewiring or mounting changes needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2220-7MS32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2220-7MS32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}