{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5HL32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5HL32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5HL32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HL32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5HL32-0AG0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 187 kA breaking capacity at 240 V.","salesMarkdown":"## Siemens 3VA2225-5HL32-0AG0 — 250 A MCCB, Active Line Protection Its breaking capacity runs from 187 kA at 240 V down to 4.5 kA at 690 V, giving you selectivity headroom across common low-voltage levels without cascading upstream. ## Breaking Capacity by Voltage Level At 415 V and 440 V the breaker holds 121 kA; at 500 V it still delivers 75.6 kA. ## Auxiliary Switching and Monitoring This variant ships with one auxiliary switch and one trip-alarm switch (HP type) — enough for remote status feedback and fault annunciation without an additional add-on module. The breaker measures 105 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA2 footprint that fits existing panel cutouts and busbar spacing for 3-pole MCCBs in that amp class. The 86 mm depth leaves clearance for rear-connected busbars or cable lugs in a typical 600 mm deep enclosure.","metaTitle":"Siemens 3VA2225-5HL32-0AG0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2225-5HL32-0AG0 molded case circuit breaker, 250 A continuous, 3-pole, 187 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2225-5HL32-0AG0","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU320, LI, In=250A overload protection Ir=100A...250A short-circuit protection Ii=1.5...10 x In nut keeper kit 1 auxiliary switch HP 1 trip alarm switch HP","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-5HL32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=441930&mlfb=3VA2225-5HL32-0AG0"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-5HL32-0AG0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What are the key ratings of this MCCB?","answer":"250 A continuous rating, 3-pole, breaking capacity of 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V."},{"question":"What is the depth of 3VA2225-5HL32-0AG0?","answer":"86 mm (3.39 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5HL32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5HL32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}