{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5HL32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5HL32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5HL32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HL32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5HL32-0JH0, molded case circuit breaker, 3-pole, 250 A, line protection, ETU320 release, shunt trip, 187 kA at 240 V interrupting rating.","salesMarkdown":"The Siemens SENTRON 3VA2225-5HL32-0JH0 is a 3-pole molded case circuit breaker rated for 250 A continuous current (Iu) at 40 °C, with the same rating holding flat through 50 °C — useful when the panel ambient runs warm but not hot. Interrupting capacity is the headline here: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V. At 690 V the 5.1 kA rating is modest; if your system runs 690 V with fault currents above that, this breaker is not the right choice for that voltage leg. The overcurrent release is an ETU320 — a basic electronic trip unit with fixed settings (no adjustable long-time, short-time, or ground-fault pickups). It is a line-protection breaker, not a motor-protection or feeder-selectivity device. There is no communication function, no phase-failure detection, and no undervoltage release fitted. No DIN-rail clip on this frame; it is screw-fixed.","metaTitle":"Siemens 3VA2225-5HL32-0JH0 MCCB, 250 A, 3-pole, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-5HL32-0JH0 molded case circuit breaker, 250 A, 3-pole, 187 kA at 240 V interrupting rating. ETU320 release, shunt trip, line protection. Sourced to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"5.1 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-5HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=190363&mlfb=3VA2225-5HL32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HL32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2225-5HL32-0JH0?","answer":"Submit an RFQ against this part; pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA2225-5HL32-0JH0's interrupting rating at 415 V?","answer":"It is rated 121 kA at 415 V, matching the 440 V rating — a strong figure for most industrial 400 V-class distribution panels."},{"question":"What auxiliary contacts are fitted on this MCCB?","answer":"The breaker ships with 2 auxiliary switches plus 1 trip alarm switch (HQ version), plus a built-in shunt trip (STL) for remote tripping."},{"question":"Does this breaker include ground-fault monitoring or communication?","answer":"No — it has no ground-fault monitoring, no communication function, no phase-failure detection, and no undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5HL32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5HL32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}