{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5HL42-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5HL42-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5HL42-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HL42-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5HL42-0JH0, molded case circuit breaker, 4-pole, 250 A rated continuous current, ETU320 release, interrupting 187 kA at 240 V.","salesMarkdown":"The interrupting ratings tell you where this breaker can be applied: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V. Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If the panel ambient runs 60 °C, size the load at 232 A continuous — not the nameplate 250 A. Both are serviceable spares if the main breaker body is in the panel and only the trip unit or aux switch needs replacement. ## What it does not include The shunt trip (STL) is the only auxiliary release fitted; if you need undervoltage protection or remote comms, this variant is not the one.","metaTitle":"Siemens 3VA2225-5HL42-0JH0 SENTRON MCCB, 250 A, 4-Pole, 187","metaDescription":"Siemens SENTRON 3VA2225-5HL42-0JH0 molded case circuit breaker, 250 A rated continuous current, 4-pole, interrupting up to 187 kA at 240 V. Current lifecycle. Sourced to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"5.1 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"Yes","Number of poles":"4","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-5HL42-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=354356&mlfb=3VA2225-5HL42-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HL42-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-5HL42-0JH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of 3VA2225-5HL42-0JH0 at 240 V?","answer":"The interrupting rating is 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V."},{"question":"Does 3VA2225-5HL42-0JH0 include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) release. There is no undervoltage release fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5HL42-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5HL42-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}