{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5HN32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5HN32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5HN32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HN32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5HN32-0AG0, 3-pole molded case circuit breaker, 250 A rated continuous current Iu, 187 kA breaking capacity at 240 V, ETU350 electronic trip unit, line protection version.","salesMarkdown":"## MCCB for high-fault panel builds The Siemens 3VA2225-5HN32-0AG0 is a 3-pole molded case circuit breaker from the SENTRON family, rated for 250 A continuous current (Iu) and carrying a 187 kA breaking capacity at 240 V — that's the short-circuit rating that governs whether this breaker clears a fault without upstream devices needing to coordinate. The interrupting rating drops as voltage rises: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V. ## Thermal derating and panel fill Above that it derates: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, 213 A at 70 °C. ## Trip unit and auxiliary contacts The breaker ships with 1 auxiliary switch and 1 trip alarm switch (HP version) — that's the contact configuration you'll use for remote status indication to a PLC or SCADA. The trip indicator is present, which helps during troubleshooting — you can visually confirm the breaker tripped on fault rather than being manually opened.","metaTitle":"Siemens 3VA2225-5HN32-0AG0 SENTRON MCCB, 250 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-5HN32-0AG0 molded case circuit breaker, 250 A rated, 187 kA breaking at 240 V, ETU350 trip unit, 3-pole, current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"5.1 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-5HN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"2 500 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"375 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=104604&mlfb=3VA2225-5HN32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5HN32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2225-5HN32-0AG0 at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 5.1 kA at 690 V. The 690 V figure is the one to verify against your available fault current."},{"question":"What trip unit does this MCCB use?","answer":"It uses the ETU350 electronic trip unit, which provides adjustable overload and short-circuit protection curves. This is the same trip platform used across the SENTRON 3VA2 family."},{"question":"Where can I buy 3VA2225-5HN32-0AG0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response."},{"question":"Does 3VA2225-5HN32-0AG0 include auxiliary contacts?","answer":"Yes, it ships with 1 auxiliary switch and 1 trip alarm switch (HP version). The base variant 3VA2225-5HN32-0AA0 omits these contacts if you need a bare breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5HN32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5HN32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}