{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5JP32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5JP32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5JP32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JP32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 250 A, 3-pole, line protection, ETU550 release, 187 kA at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"The Siemens 3VA2225-5JP32-0KL0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a 3-pole configuration and an ETU550 electronic trip unit. The 250 A rating holds flat from 40 °C to 50 °C, then derates to 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. The interrupting curve drops from 187 kA at 240 V to 121 kA at 415/440 V, then 79 kA at 500 V, and 5.1 kA at 690 V. At 690 V the breaker still clears faults, but the available fault current must stay under 5.1 kA. A voltage trigger is present, and the trip indicator gives a local visual flag after a fault. The ETU550 electronic overcurrent release provides adjustable LSI protection curves — suitable for selective coordination in a distribution board. The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that fits most 600 V switchboard buckets and DIN-rail adapters.","metaTitle":"Siemens 3VA2225-5JP32-0KL0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens 3VA2225-5JP32-0KL0 SENTRON molded case circuit breaker, 250 A rated continuous current, 3-pole, 187 kA at 240 V. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"5.1 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-5JP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=219678&mlfb=3VA2225-5JP32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JP32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-5JP32-0KL0 and how is it quoted?","answer":"This part is sourced through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time against an RFQ — no online stock figure or shelf count is published here."},{"question":"What is the interrupting capacity of 3VA2225-5JP32-0KL0 at 415 V?","answer":"121 kA at 415 V and 440 V. At 240 V it reaches 187 kA; at 500 V it drops to 79 kA; at 690 V the rating is 5.1 kA."},{"question":"What trip unit does 3VA2225-5JP32-0KL0 use?","answer":"An ETU550 electronic overcurrent release with LSI protection curves. The breaker is configured for line protection duty."},{"question":"Does 3VA2225-5JP32-0KL0 include auxiliary contacts?","answer":"Yes — 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type). A shunt trip release is also fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5JP32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5JP32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}