{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5JP42-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5JP42-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5JP42-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JP42-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5JP42-0KH0, molded case circuit breaker, 4-pole, 250 A rated, 187 kA breaking capacity at 240 V AC, line protection design, with communication function and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2225-5JP42-0KH0 is a 4-pole molded case circuit breaker (MCCB) rated for continuous 250 A at 40 °C, with a breaking capacity of 187 kA at 240 V AC. That 250 A continuous rating holds up to 50 °C without derating; above that the curve steps down to 200 A at 70 °C (–). ## Accessories and wiring No undervoltage release is included — if you need UVR, plan for an external add-on.","metaTitle":"Siemens 3VA2225-5JP42-0KH0 SENTRON MCCB, 250A, 4P, 187kA@240","metaDescription":"Siemens SENTRON 3VA2225-5JP42-0KH0 molded case circuit breaker, 250 A rated, 4-pole, 187 kA breaking at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"#BEZUG!","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 100%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=811827&mlfb=3VA2225-5JP42-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JP42-0KH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2225-5JP42-0KH0?","answer":"Submit an RFQ through this listing. Availability and pricing are confirmed at quote time through independent distribution channels."},{"question":"Will 3VA2225-5JP42-0KH0 drop into a panel specified around 3VA2225-5HN42-0BB0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA2 breakers with the same physical footprint (86 mm depth, 140 mm width, 181 mm height), so mechanical fit is identical. The difference is in the internal trip unit and accessories: 3VA2225-5JP42-0KH0 carries a shunt trip (STL) and communication function, while the -5HN42-0BB0 variant omits those. Wiring for the power terminals is the same; control wiring for the shunt trip and comms must be added if those features are needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5JP42-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5JP42-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}