{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5JQ32-0DE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5JQ32-0DE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5JQ32-0DE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JQ32-0DE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250 circuit breaker, breaking capacity class M, Icu=55kA @ 415V, 3-pole, ETU560 LSIG, In=250A, with undervoltage release 208-230V AC 50/60Hz and 4 auxiliary switches.","salesMarkdown":"The Siemens 3VA2225-5JQ32-0DE0 is a 3-pole IEC frame 250 molded-case circuit breaker with a breaking capacity class M rating of Icu=55kA at 415V AC. For a 400V industrial distribution board fed by a transformer in the 1.5–2 MVA range, that's enough headroom to avoid cascading upstream. The ETU560 electronic trip unit gives you LSIG protection: long-time (overload), short-time (short-circuit with adjustable delay), instantaneous, and ground-fault. In=250A, with overload protection Ir adjustable from 100A to 250A, short-circuit protection ISD from 0.6 to 10×In, and instantaneous pickup II from 1.5 to 10×In. Ground-fault protection can be switched off, with IG adjustable 0.2 to 1×In and time delay TG at 0.05 or 0.8 seconds. The built-in undervoltage release (208–230V AC 50/60 Hz) and four auxiliary switches round out the package for remote status and shunt-trip capability. ## Deployment context The ETU560 LSIG trip unit is field-adjustable, so you can dial in the protection curve to match downstream loads without swapping the breaker. The undervoltage release (208–230V AC) provides automatic trip on loss of control voltage — typical for safety circuits or emergency-stop chains.","metaTitle":"Siemens 3VA2225-5JQ32-0DE0 3VA2 IEC Frame 250, 55kA @ 415V,","metaDescription":"Siemens 3VA2225-5JQ32-0DE0 circuit breaker, 3VA2 IEC frame 250, breaking capacity class M, Icu=55kA @ 415V, 3-pole, ETU560 LSIG, In=250A. Current lifecycle stage. Available to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=908317&mlfb=3VA2225-5JQ32-0DE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JQ32-0DE0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The ultimate short-circuit breaking capacity (Icu) is 55 kA at 415V AC, class M per IEC 60947-2."},{"question":"What trip unit does this breaker use?","answer":"It uses the ETU560 electronic trip unit with LSIG protection: long-time, short-time, instantaneous, and ground-fault. In=250A, Ir adjustable 100–250A, ISD 0.6–10×In, II 1.5–10×In, IG 0.2–1×In, TG 0.05 or 0.8 s."},{"question":"Where can I buy 3VA2225-5JQ32-0DE0?","answer":"This part is sourced and quoted to order through independent distribution against an RFQ. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5JQ32-0DE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5JQ32-0DE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}