{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-5JQ32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-5JQ32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-5JQ32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JQ32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-5JQ32-0DL0 molded case circuit breaker, 3-pole, 250 A adjustable trip (50–250 A), 187 kA at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"## Siemens 3VA2225-5JQ32-0DL0 — SENTRON MCCB, 250 A, 3-Pole The Siemens 3VA2225-5JQ32-0DL0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 250 A at 40 °C and an adjustable thermal-magnetic trip range from 50 A to 250 A. The 3-pole design fits standard 3-phase distribution panels, and the built-in undervoltage release (UVR) drops the breaker if control voltage is lost — a common requirement for emergency-stop circuits. The 250 A rating holds flat from 40 °C to 50 °C, then derates to 200 A at 70 °C — so in a warm enclosure you lose 50 A of headroom. The adjustable trip (50–250 A) lets you match the breaker to the actual load without swapping hardware, but the full-scale value of 250 A sets the maximum continuous current. The 187 kA SCCR at 240 V is typical for a large service entrance; at 690 V it drops to 4.5 kA, so on 690 V systems this breaker is only suitable for low-fault locations. The undervoltage release (UVR) is factory-fitted; verify control voltage matches the coil rating before energizing. The maximum power loss of 50.5 W means the breaker contributes noticeable heat — account for it in the enclosure thermal calculation.","metaTitle":"Siemens 3VA2225-5JQ32-0DL0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2225-5JQ32-0DL0 molded case circuit breaker, 250 A, 3-pole, 187 kA at 240 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"50 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"250 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-5JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=53351&mlfb=3VA2225-5JQ32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-5JQ32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-5JQ32-0DL0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing."},{"question":"What is 3VA2225-5JQ32-0DL0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in)."},{"question":"What is 3VA2225-5JQ32-0DL0's listed width (105 mm) on this component line?","answer":"The width is 105 mm (4.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-5JQ32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-5JQ32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}