{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2225-6HL32-0AA0, 250 A, 3-pole, ETU320 electronic trip unit, line protection, 242 kA at 240 V.","salesMarkdown":"## MCCB for line protection — 250 A frame, ETU320 trip unit The Siemens 3VA2225-6HL32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a 3-pole configuration and an ETU320 electronic overcurrent release. ## Thermal derating and ambient limits Above that, it derates linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C.","metaTitle":"Siemens 3VA2225-6HL32-0AA0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens 3VA2225-6HL32-0AA0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, ETU320 release, 242 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$490.22","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=174137&mlfb=3VA2225-6HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6HL32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2225-6HL32-0AA0's listed depth?","answer":"The depth is 86 mm (3.39 in)."},{"question":"What is 3VA2225-6HL32-0AA0's listed width?","answer":"The width is 105 mm (4.13 in)."},{"question":"Will 3VA2225-6HL32-0AA0 drop into a panel that was specified around 5SQ2370-2YA05 without rewiring?","answer":"Yes, the 3VA2225-6HL32-0AA0 is a direct functional equivalent to the 5SQ2370-2YA05 — same 250 A frame, 3-pole, similar interrupting ratings. The dimensions (105 mm wide, 181 mm tall, 86 mm deep) match the standard 3VA2 footprint, so it should fit the same panel cutout and bus connections without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}