{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HL32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HL32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6HL32-0BA0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 242 kA breaking capacity at 240 V, undervoltage release, ETU320 overcurrent release.","salesMarkdown":"The Siemens SENTRON 3VA2225-6HL32-0BA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current, with a breaking capacity of 242 kA at 240 V — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. At 40 °C ambient the breaker carries the full 250 A; it holds that rating through 50 °C, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. If your panel runs hot, factor the 55 °C curve for a 241 A continuous limit. Maximum power loss is 50.5 W — modest for a 250 A frame, but if you pack multiple breakers in a small enclosure, that heat adds up. Plan ventilation or derate accordingly. The 3VA2225-6HL32-0BA0 measures 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole MCCB footprint that drops into most SENTRON panelboards and distribution blocks without re-drilling gland plates.","metaTitle":"Siemens 3VA2225-6HL32-0BA0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6HL32-0BA0 molded case circuit breaker, 250 A rated continuous current, 242 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"50.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=228846&mlfb=3VA2225-6HL32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2225-6HL32-0BA0 at 240 V?","answer":"242 kA at 240 V, which covers high-fault utility feeds and large transformer secondaries."},{"question":"Where can I buy 3VA2225-6HL32-0BA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3VA2225-6HL32-0BA0 drop into a panel specified around 3VA1112-5EF32-0CA0?","answer":"Both are SENTRON 3VA series MCCBs with the same 3-pole form factor, so the footprint and mounting are identical. The main difference is the rating — the 3VA2225 carries 250 A versus the lower-rated 3VA1112 frame."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HL32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}