{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HL32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HL32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6HL32-0BL0, 3-pole molded case circuit breaker, 250 A continuous rating, line protection design, 242 kA breaking capacity at 240 V AC, undervoltage release, auxiliary switches.","salesMarkdown":"Breaking capacity drops from 242 kA at 240 V to 187 kA at 415/440 V, then to 121 kA at 500 V, and 4.5 kA at 690 V. The steep fall at 690 V means this breaker is optimized for 240–500 V systems; at 690 V the SCCR is only 4.5 kA, so verify the available fault current if deploying on a 690 V line. The adjustable thermal-magnetic trip unit covers 375 A to 2 500 A maximum setting range, giving flexibility to coordinate with downstream breakers in a selective distribution scheme. Rated 250 A continuous from 40 °C up to 50 °C ambient, then derates linearly to 213 A at 70 °C. In a sealed panel with poor airflow, expect to apply the 70 °C column. Maximum power loss is 50.5 W at rated current — factor this into enclosure thermal calculations, especially when grouping multiple breakers.","metaTitle":"Siemens 3VA2225-6HL32-0BL0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6HL32-0BL0 molded case circuit breaker, 250 A continuous, 242 kA breaking at 240 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=318978&mlfb=3VA2225-6HL32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6HL32-0BL0 and how do I get a price?","answer":"Sourced to order against an RFQ through independent distribution channels. Submit a request for quote with your target quantity and delivery window; availability and current pricing are confirmed at quote time."},{"question":"When sourcing 3VA2225-6HL32-0BL0, what's the closest functional alternative?","answer":"The 3VA2225-5HN42-0BB0 is a peer variant in the same 3VA2225 frame but with a different trip unit and accessory configuration. It shares the same 250 A frame size and 3-pole form factor, so it drops into the same panel cutout and busbar pattern, but verify the trip curve and auxiliary switch count match your BOM before substituting."},{"question":"What is the depth of this MCCB?","answer":"86 mm (3.39 in) deep, which is shallow enough for standard 600 mm deep enclosures with cable bending radius clearance behind the breaker."},{"question":"What compliance documentation does Siemens provide for this breaker?","answer":"As a standard SENTRON MCCB, it carries IEC 60947-2 certification and UL 489 listing. RoHS and REACH declarations are available through Siemens Industry Online Support. No specific document numbers are on this listing, but the brand provides full compliance packages on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HL32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}