{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HL32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HL32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2225-6HL32-0JA0, 250 A rated, 3-pole, line protection, ETU320 overcurrent release, integrated shunt trip STL, 242 kA interrupting at 240 V.","salesMarkdown":"Interrupting capacity is the headline here: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and still 6 kA at 690 V. The 250 A frame stays fully rated across the 40 °C to 50 °C ambient band; derating starts at 55 °C (241 A) and drops to 213 A by 70 °C. ## Trip unit and release configuration The shunt trip (STL) is integrated, not an add-on module, and its part number is 3VA9688-0BL32. No undervoltage release, no phase-failure detection, no ground-fault module on this variant. The base switch itself is order code 3VA2225-6HL32-0AA0. Maximum power loss is 48 W. Mechanical endurance is 20,000 operations. Three-pole footprint, so it occupies a standard MCCB slot in a SENTRON distribution panel or any DIN-rail-mounting enclosure rated for the frame size. Lifecycle status is current — this is an active, in-production Siemens SENTRON catalog number.","metaTitle":"Siemens 3VA2225-6HL32-0JA0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6HL32-0JA0 molded case circuit breaker, 250 A rated, 3-pole, line protection with ETU320 trip unit and shunt trip. SCCR 242 kA at 240 V. Active production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=481002&mlfb=3VA2225-6HL32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VA2225-6HL32-0JA0 include a shunt trip?","answer":"Yes, it has an integrated shunt trip release (STL), design code 3VA9688-0BL32. No undervoltage release or ground-fault module on this variant."},{"question":"What are the physical dimensions — depth, width, height?","answer":"Depth is 86 mm, width 105 mm, height 181 mm. Three-pole footprint fits standard SENTRON panel slots."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HL32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}