{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HL32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HL32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 250 A, 3-pole, line protection, ETU320 electronic trip, shunt trip (STL), 2 auxiliary switches HQ, 242 kA at 240 V.","salesMarkdown":"The 250 A rating holds across 40 °C to 50 °C (–), then derates linearly to 213 A at 70 °C — so if your panel ambient runs hot, you'll need to account for that. Breaking capacity drops from 242 kA at 240 V to 187 kA at 415 V and 6 kA at 690 V; the 690 V figure is low, so this breaker is best suited for 240–480 V systems where the high interrupt rating matters. The 3-pole frame mounts via screw terminals or plug-in base; no DIN-rail mounting on this class. Plan for 48 W maximum power loss in the enclosure thermal budget.","metaTitle":"Siemens 3VA2225-6HL32-0JC0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens 3VA2225-6HL32-0JC0 SENTRON molded case circuit breaker, 250 A rated at 40 °C, 242 kA breaking at 240 V. ETU320 release, shunt trip, 2 HQ aux. Active production. Request quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=243265&mlfb=3VA2225-6HL32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HL32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2225-6HL32-0JC0 at 240 V?","answer":"242 kA at 240 V, dropping to 187 kA at 415 V and 6 kA at 690 V. The high 240 V rating suits it for heavy fault-current applications like transformer secondaries or large motor starters."},{"question":"How do I get pricing and availability for 3VA2225-6HL32-0JC0?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; current pricing and lead time are confirmed at quote time."},{"question":"What auxiliary options are built into 3VA2225-6HL32-0JC0?","answer":"It includes a shunt trip (STL) release for remote tripping and two HQ auxiliary switches for status indication. No undervoltage release or communication function is fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HL32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HL32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}