{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HN32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HN32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2225-6HN32-0CA0, 3-pole, 250 A rated continuous current, line protection with ETU350 electronic trip unit, 242 kA breaking capacity at 240 V, 105 x 181 x 86 mm.","salesMarkdown":"Its 250 A continuous current holds flat from 40 °C to 50 °C, then derates to 213 A at 70 °C — useful to know if your panel runs hot or is packed tight. An undervoltage release (UVR) is integrated as standard — the UVR coil is part of the basic switch assembly. No auxiliary contacts or communication module are fitted on this variant. The depth of 86 mm means it clears most 200 mm deep enclosures, but check your gland-plate clearance if the panel is shallow. Maximum power loss is 50.5 W, so factor that into your thermal budget if grouping multiple breakers.","metaTitle":"Siemens 3VA2225-6HN32-0CA0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens 3VA2225-6HN32-0CA0 SENTRON molded case circuit breaker, 250 A rated at 40 °C, 3-pole, line protection with ETU350 trip unit. Breaking capacity 242 kA at 240 V. Current life","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"50.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"2 500 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"375 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=96099&mlfb=3VA2225-6HN32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6HN32-0CA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA2225-6HN32-0CA0 at 240 V?","answer":"The breaking capacity is 242 kA at 240 V, which handles high-fault scenarios typical of large transformer secondaries or busway feeds."},{"question":"Does 3VA2225-6HN32-0CA0 include an undervoltage release?","answer":"Yes, an undervoltage release (UVR) is integrated as standard, part of the basic switch assembly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HN32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}