{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HN32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HN32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6HN32-0CL0, molded case circuit breaker, 3-pole, 250 A rated at 40 °C, interrupting 242 kA at 240 V, with undervoltage release and auxiliary switch configuration.","salesMarkdown":"The Siemens SENTRON 3VA2225-6HN32-0CL0 is a 3-pole molded case circuit breaker rated for 250 A continuous at 40 °C, with a maximum interrupting capacity of 242 kA at 240 V. This is a line-protection design (not a motor-protection breaker), so it's sized for feeder or main service entrance duty. The case measures 105 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA2 frame size that fits the same mounting footprint as other 250 A MCCBs in the family. That 86 mm depth (3.39 in) is the dimension that matters when the gland plate or enclosure door clearance is tight. The breaker ships with the basic switch 3VA2225-6HN32-0AA0 as the supplied switching element; the order code suffix -0CL0 adds the specific UVR and auxiliary contact configuration.","metaTitle":"3VA2225-6HN32-0CL0 SENTRON MCCB, 250A, 3-Pole, 242kA at 240V","metaDescription":"Siemens SENTRON 3VA2225-6HN32-0CL0 molded case circuit breaker, 250A continuous, 3-pole, 242kA interrupting at 240V. Active production. Available to order, RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"2 500 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=68748&mlfb=3VA2225-6HN32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2225-6HN32-0CL0?","answer":"It is a 3-pole MCCB rated 250 A continuous at 40 °C, with interrupting capacity of 242 kA at 240 V, 187 kA at 415 V, and 121 kA at 500 V. It includes an undervoltage release and a 2+1+1 auxiliary switch configuration."},{"question":"Where can I buy 3VA2225-6HN32-0CL0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the depth of 3VA2225-6HN32-0CL0?","answer":"The depth is 86 mm (3.39 in). Width is 105 mm (4.13 in) and height is 181 mm (7.13 in)."},{"question":"Will 3VA2225-6HN32-0CL0 drop into a panel specified around 5SQ2370-2YA05?","answer":"The 3VA2225-6HN32-0CL0 is a SENTRON frame-size MCCB; the 5SQ2370-2YA series are from a different product family. Physical interchangeability depends on the mounting base and bus-bar arrangement in the existing panel — verify the cutout dimensions and lug spacing before ordering as a drop-in replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HN32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}