{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6HN32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6HN32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6HN32-0DL0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"At 690 V it holds 4.5 kA, so this is a low-voltage main or feeder breaker, not a motor-circuit device. Above that it derates linearly: 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, 213 A at 70 °C. Physical footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard SENTRON 3VA frame size for 250 A. Fits the same panel cutout and busbar spacing as other 3VA2 breakers in this current class. ## Internal accessories — what ships inside the frame The UVR drops the breaker on loss of control voltage — standard for safety disconnects on conveyor or press feeds where a voltage dip must open the main. The base switch mechanism is order code 3VA2225-6HN32-0AA0. That's the heat the breaker dumps into the enclosure — factor it into your panel thermal calculation, especially if the cabinet is sealed or stacked with multiple breakers. The storage limit governs shipping and warehousing, not running conditions. ## Lifecycle and sourcing — active, quoted to order If you need ground-fault detection, this is not the right suffix.","metaTitle":"Siemens 3VA2225-6HN32-0DL0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2225-6HN32-0DL0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"2 500 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=437257&mlfb=3VA2225-6HN32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6HN32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6HN32-0DL0 and how do I get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not listed here."},{"question":"What is 3VA2225-6HN32-0DL0's listed depth?","answer":"Depth is 86 mm (3.39 in), width 105 mm (4.13 in), height 181 mm (7.13 in). Fits standard SENTRON 3VA2 panel cutouts."},{"question":"What breaking capacity does this MCCB deliver at 415 V?","answer":"187 kA at 415 V, same as at 440 V. At 240 V it reaches 242 kA; at 500 V it drops to 121 kA; at 690 V it holds 4.5 kA."},{"question":"Will 3VA2225-6HN32-0DL0 drop into a panel specified around 3VA2116-5HL32-0AK0?","answer":"No — the 3VA2225 is a 250 A frame (105 mm wide); the 3VA2116 is a 160 A frame with different busbar spacing and cutout dimensions. They are not mechanically interchangeable without panel modification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6HN32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6HN32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}