{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0AE0, molded case circuit breaker, 250 A, 3-pole, line protection, with communication function, 242 kA breaking at 240 V.","salesMarkdown":"This MCCB delivers 242 kA breaking capacity at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. At 690 V the 4.5 kA rating is modest; verify the system's prospective short-circuit current at that voltage before specifying. In a sealed, high-ambient panel — common in process plants or near ovens — the 70 °C derated figure (200 A) is the one to size your load against. Maximum power loss is 48 W, which contributes to enclosure heat rise and should be factored into the thermal budget.","metaTitle":"Siemens 3VA2225-6JP32-0AE0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0AE0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=8743&mlfb=3VA2225-6JP32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JP32-0AE0 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"187 kA at 415 V, matching the rating at 440 V. At 240 V it reaches 242 kA."},{"question":"Does this breaker support communication?","answer":"Yes, it includes a communication function for integration into networked energy management systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}