{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0BG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0BG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0BG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0BG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0BG0, Molded case circuit breaker, 3-pole, Line protection, 250 A, ETU550, 242 kA at 240 V, 187 kA at 415 V, 4.5 kA at 690 V, Undervoltage release, Communication function, IP40 front.","salesMarkdown":"It's a line-protection breaker — meaning it's set up for cable and busbar protection, not motor overload duty. The interrupting ratings are the headline: 242 kA at 240 V, 187 kA at 415 V, and 4.5 kA at 690 V. The 690 V rating drops to 4.5 kA, which is still useful for 690 V drives or transformer secondaries but not for high-fault locations on that voltage class. It also carries a communication function, so it can talk to a higher-level control system for trip data and remote monitoring — useful when you're coordinating a whole switchboard and want event logs without walking the floor. Full 250 A rating holds through 50 °C ambient. Above that it steps down: 240.625 A at 55 °C, 231.25 A at 60 °C, 221.875 A at 65 °C, and 212.5 A at 70 °C. The maximum power loss is 55 W, which is modest for a 250 A frame but still needs ventilation in a sealed box.","metaTitle":"3VA2225-6JP32-0BG0 SENTRON MCCB, 250 A, 3-pole, ETU550","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0BG0 molded case circuit breaker, 250 A rated, 3-pole, ETU550 trip unit, 242 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"107 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240.625 A","at 60 °C":"231.25 A","at 65 °C":"221.875 A","at 70 °C":"212.5 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"55 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"1 A","Adjustable response value current / li min.":"1.5 A","Adjustable response value current / lr min.":"0.4 A","Adjustable response value current / Isd max.":"10 A","Adjustable response value current / Isd min.":"0.6 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=304453&mlfb=3VA2225-6JP32-0BG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0BG0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JP32-0BG0 and what's the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but we can get you a firm position within a business day."},{"question":"What are the key interrupting ratings for 3VA2225-6JP32-0BG0?","answer":"242 kA at 240 V, 187 kA at 415 V, and 4.5 kA at 690 V. The 415 V figure is the one that governs most 400 V distribution panels."},{"question":"What trip unit does this MCCB use?","answer":"The ETU550 — a microprocessor-based electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection, plus communication capability for remote monitoring."},{"question":"What are the physical dimensions of 3VA2225-6JP32-0BG0?","answer":"105 mm wide, 181 mm tall, 107 mm deep — standard 3-pole MCCB footprint."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it ships with an undervoltage release (UVR) as standard, plus one auxiliary switch and one trip-alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0BG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0BG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}