{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0CL0, molded case circuit breaker, 3-pole, 250 A rated continuous current, ETU550 electronic trip unit, line protection, 242 kA breaking capacity at 240 V.","salesMarkdown":"The Siemens 3VA2225-6JP32-0CL0 is a SENTRON molded case circuit breaker rated for 250 A continuous current (Iu) with an ETU550 electronic trip unit. The 3-pole line-protection variant is sized for feeder or main breaker duty in distribution panels. Breaking capacity drops as system voltage rises: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V. The 187 kA figure at 415 V is the one most European industrial panels will coordinate against — it tells you this breaker holds its own on the secondary side of a 500 kVA transformer without needing a current-limiting upstream device. Rated 250 A from 40 °C through 50 °C ambient. Above that, derating is linear: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. If this breaker lives in a non-air-conditioned enclosure near ovens or drives, the 55 °C derated figure (238 A) is the one to size the downstream load against — not the 250 A nameplate. ## Trip unit and auxiliary configuration This order code ships with an undervoltage release (UVR) fitted, plus a full auxiliary contact block: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type). Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard 3-pole MCCB footprint that fits SENTRON 3VA mounting bases and busbar systems.","metaTitle":"Siemens 3VA2225-6JP32-0CL0 SENTRON MCCB, 250 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0CL0 molded case circuit breaker, 250 A rated continuous current, 242 kA breaking at 240 V, 3-pole, ETU550 trip unit, line protection. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"50.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=409153&mlfb=3VA2225-6JP32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA2225-6JP32-0CL0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What are the key ratings of 3VA2225-6JP32-0CL0?","answer":"Rated continuous current 250 A, breaking capacity 242 kA at 240 V, 187 kA at 415 V, 3-pole, ETU550 electronic trip unit with undervoltage release and full auxiliary contact block."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON series MCCB, it carries IEC 60947-2 certification and UL 489 listing where applicable. RoHS and REACH declarations are available from Siemens documentation portals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}