{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0HA0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA breaking at 240 V, shunt trip, line protection.","salesMarkdown":"## MCCB with high interrupting capacity for line protection The Siemens SENTRON 3VA2225-6JP32-0HA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, with a shunt trip release for remote opening. Its interrupting capacity hits 242 kA at 240 V AC and 187 kA at 415 V AC, which means it can clear high-fault currents on a distribution bus without cascading upstream — critical for selective coordination in a plant main or feeder panel. The unit measures 105 mm wide by 181 mm tall by 86 mm deep, fitting standard panel cutouts for SENTRON 3VA frames. Above that, it derates linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss is 48 W. Interrupting ratings: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. The steep drop at 690 V (4.5 kA) is typical for an MCCB with a 250 A frame — the arc extinction limits at higher voltage. For a 480 V or 600 V class system, the 121 kA at 500 V gives ample headroom for most industrial services.","metaTitle":"Siemens 3VA2225-6JP32-0HA0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0HA0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Shunt trip, line protection. Current production. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=317494&mlfb=3VA2225-6JP32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JP32-0HA0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source to 3VA2225-6JP32-0HA0?","answer":"The peer MPNs 5SQ2370-2YA05, 5SQ2370-2YA04, and 5SQ2370-2YA01 are listed as related, but no direct functional cross-reference is documented. Panel fit and ratings should be verified before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}