{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0JH0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"The Siemens SENTRON 3VA2225-6JP32-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 250 A continuous at 40 °C through 50 °C without derating. At 240 V it interrupts 242 kA — that's the short-circuit rating that governs fault clearance upstream of a transformer or a high-fault panel. At 415 V and 440 V it holds 187 kA, dropping to 121 kA at 500 V and 4.5 kA at 690 V. Thermal derating starts at 55 °C — 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, 200 A at 70 °C. The 105 mm width per pole (35 mm per pole) is standard for SENTRON 3VA breakers; a 3-pole unit occupies three 35 mm DIN slots if base-mounted, or bolts directly to a mounting plate.","metaTitle":"Siemens 3VA2225-6JP32-0JH0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0JH0 molded case circuit breaker, 250 A continuous, 242 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=12034&mlfb=3VA2225-6JP32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JP32-0JH0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What is the interrupting capacity of 3VA2225-6JP32-0JH0 at 240 V?","answer":"242 kA at 240 V. That is the highest short-circuit rating in the 3VA 250 A frame — it can clear a fault on a high-capacity transformer secondary without upstream fusing."},{"question":"Does 3VA2225-6JP32-0JH0 include auxiliary contacts?","answer":"Yes, it comes with two auxiliary switches plus one trip alarm switch (HQ). The shunt trip (STL) release is also integrated, so remote tripping and status feedback are available without an external module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}