{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0KC0, molded case circuit breaker, 3-pole, 250 A, interrupting 242 kA at 240 V, 187 kA at 415 V, 4.5 kA at 690 V, with shunt trip and communication function.","salesMarkdown":"The Siemens SENTRON 3VA2225-6JP32-0KC0 is a 3-pole molded case circuit breaker rated for 250 A continuous at 40 °C, with a thermal derating curve that holds 250 A up to 50 °C and drops to 200 A at 70 °C — so in a warm enclosure you size for the actual ambient, not the nameplate. The interrupting ratings are what decide whether this breaker clears a fault without welding its contacts or venting arc gas: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. That spread means the breaker is designed for high-fault-current 480 V and 600 V class panels where the available fault current can exceed 100 kA; at 690 V the interrupting capacity drops sharply, so verify the SCCR at that voltage before specifying it for 690 V switchgear. ## Built-in accessories and panel fit The communication function is present, so it can report status or accept remote trip commands over the SENTRON bus. Dimensions are 105 mm wide, 181 mm high, 86 mm deep; it mounts on a DIN rail or direct panel, and the 3-pole footprint matches the standard SENTRON 3VA223 frame.","metaTitle":"Siemens 3VA2225-6JP32-0KC0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0KC0 molded case circuit breaker, 3-pole, 250 A continuous, 242 kA interrupting at 240 V. Current lifecycle. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=506547&mlfb=3VA2225-6JP32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JP32-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2225-6JP32-0KC0 at 415 V?","answer":"187 kA at 415 V."},{"question":"What is the continuous current rating of 3VA2225-6JP32-0KC0?","answer":"250 A at 40 °C, with derating to 200 A at 70 °C."},{"question":"Does 3VA2225-6JP32-0KC0 include a shunt trip?","answer":"Yes, it includes a shunt trip (STL) release and two HQ auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}