{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JP32-0LK0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JP32-0LK0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0LK0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JP32-0LK0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JP32-0LK0, molded case circuit breaker, 3-pole, 250 A, interrupting rating 242 kA at 240 V, ETU550 electronic trip unit, line protection version.","salesMarkdown":"The Siemens SENTRON 3VA2225-6JP32-0LK0 is a 3-pole molded case circuit breaker rated 250 A continuous at 40 °C, with an ETU550 electronic trip unit configured for line protection. The 105 mm width and 181 mm height match the standard SENTRON 3VA frame footprint, so it swaps into an existing 3VA panel cutout without re-drilling the gland plate. Full 250 A rating holds through 50 °C ambient. Above that it derates linearly: 238 A at 55 °C, 225 A at 60 °C, down to 200 A at 70 °C.","metaTitle":"Siemens 3VA2225-6JP32-0LK0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2225-6JP32-0LK0 molded case circuit breaker, 250 A, 3-pole, 242 kA interrupting at 240 V. ETU550 trip unit, line protection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2225-6JP32-0LK0","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class H Icu=85kA @ 415 V 3pole, line protection ETU550, LSI, In=250A overload protection Ir=100A...250A short circuit protection Isd=0,6..10x In, iI=1,5..10x In neutral protection optional with ext. ct,upto 160% busbar connection circuit breaker 3VA2 IEC frame 250 breaking capacity class H Icu=85kA @ 415 V 3pole, line protection ETU550, LSI, In=250A overload protection Ir=100A universal release 24 V DC accessory for 3VA1 100/160 3VA2 1 auxilia","Trip Indicator":"Yes","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","Auxiliary contact version":"1 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"#BEZUG!","Courant permanent assigné Iu":"250 A","Design Of The Auxiliary Release":"universal trigger (UNI)","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9908-0BD12","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"250 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1207919&mlfb=3VA2225-6JP32-0LK0"},"ai":{"faq":[{"question":"What is 3VA2225-6JP32-0LK0's listed depth?","answer":"86 mm (3.39 in)."},{"question":"What is 3VA2225-6JP32-0LK0's listed width?","answer":"105 mm (4.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JP32-0LK0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JP32-0LK0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}