{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2225-6JQ32-0AC0, 3-pole, 250 A, ETU560 electronic trip unit, line protection, 242 kA at 240 V.","salesMarkdown":"The Siemens 3VA2225-6JQ32-0AC0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 250 A through 50 °C with no derating — at 55 °C it still holds 238 A, and at 70 °C it delivers 200 A. That thermal curve means this breaker handles a 250 A bus in a warm panel without stepping down to a smaller frame. Three poles, 800 V rated insulation voltage, and a 48 W max power loss. The interrupting ratings climb to 242 kA at 240 V and 187 kA at 415 V and 440 V, then drop to 121 kA at 500 V and 6 kA at 690 V — that 690 V figure is the weak point; if your system runs at 690 V, this frame is not your high-fault pick. The auxiliary contact version is two HQ auxiliary switches. Communication function is present — this breaker talks to a BMS or PLC for remote monitoring and trip events. Same 250 A frame, same ETU560 trip unit, same 3-pole layout. Both share the 105 x 181 x 86 mm envelope.","metaTitle":"Siemens 3VA2225-6JQ32-0AC0 SENTRON MCCB, 250 A, 3-Pole, ETU5","metaDescription":"Siemens 3VA2225-6JQ32-0AC0 SENTRON molded case circuit breaker, 250 A rated at 40-50 °C, 3-pole, ETU560 trip unit, 242 kA at 240 V. Current lifecycle. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Summation current formation L-conductor","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / lg max.":"250 A","Adjustable response value current / lg min.":"50 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSIG","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=417003&mlfb=3VA2225-6JQ32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2225-6JQ32-0AC0 drop into a panel designed for 3VA2225-5JQ32-0AK0?","answer":"Yes, the mechanical envelope is identical — 105 mm wide, 181 mm high, 86 mm deep. Same frame size, same bus-bar spacing. No rewiring or panel modification needed for the physical fit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}