{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2225-6JQ32-0AE0, 250 A, 3-pole, 187 kA at 415 V, line protection, with communication function.","salesMarkdown":"Three poles, solid-state trip, and a communication function (cites:) let you tie it into a BMS or SCADA for remote monitoring. The 105 mm width and 181 mm height (cites:,) mean it fits standard SENTRON panel cutouts; depth is 86 mm (cites:). At 55 °C it derates to 238 A (cites:), at 60 °C to 225 A (cites:), at 65 °C to 213 A (cites:), and at 70 °C to 200 A (cites:). If your panel is in a hot machine room or near a furnace, size the load accordingly — the 250 A nameplate only applies when ambient stays at or below 50 °C. The maximum power loss is 48 W (cites:), so ventilation in the enclosure matters; don't bury it in a sealed box without airflow. The interrupting rating changes with system voltage: 242 kA at 240 V (cites:), 187 kA at 415 V and 440 V (cites:,), 121 kA at 500 V (cites:), and 4.5 kA at 690 V (cites:). For a 480 V panel you're looking at 187 kA — that's plenty for most industrial services.","metaTitle":"Siemens 3VA2225-6JQ32-0AE0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2225-6JQ32-0AE0 molded case circuit breaker, 250 A rated at 40 °C, 3-pole, 187 kA breaking at 415 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"50 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"250 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=418330&mlfb=3VA2225-6JQ32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2225-6JQ32-0AE0?","answer":"We source this part to order against an RFQ. Submit a request and we'll confirm current pricing and availability at that time."},{"question":"What is 3VA2225-6JQ32-0AE0's listed depth (86 mm) on this component line?","answer":"The listed depth is 86 mm (3.39 inches) (cites:,). Width is 105 mm (4.13 inches) and height is 181 mm (7.13 inches) (cites:,)."},{"question":"Will 3VA2225-6JQ32-0AE0 drop into a panel that was specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Both are SENTRON 3VA frame breakers with similar mounting footprints, but the 3VA2225-6JQ32-0AE0 is a higher-current variant (250 A vs the 3VA2116's lower rating). Physical dimensions differ — verify the cutout and bus bar spacing against the panel drawing before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}