{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JQ32-0CL0, molded case circuit breaker, 250 A full-scale, 3-pole, line protection design, 242 kA interrupting at 240 V.","salesMarkdown":"Its headline current rating is 250 A at 40 °C, holding flat through 50 °C before it begins to derate — at 55 °C it carries 238 A, at 60 °C it carries 225 A, and at 70 °C it carries 200 A. That derating curve is what matters for a panel sitting near a motor drive or transformer: you size the breaker for the actual ambient inside the enclosure, not the nameplate 250 A. Interrupting capacity is where this frame earns its place. At 240 V it clears 242 kA; at 415 V and 440 V it clears 187 kA; at 500 V it clears 121 kA. The 3-pole construction and undervoltage release (UVR) trip the breaker on loss of control voltage — standard for safety circuits that must fail to a de-energized state.","metaTitle":"3VA2225-6JQ32-0CL0 SENTRON MCCB, 250 A, 3-Pole, Line Protect","metaDescription":"Siemens SENTRON 3VA2225-6JQ32-0CL0 molded case circuit breaker, 250 A, 3-pole, line protection. Breaking capacity 242 kA at 240 V. Current lifecycle stage. Quoted to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2225-6JQ32-0CL0","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU560, LSIG, In=250A overload protection Ir=100A...250A short-circuit protection Isd=0.6..10x In, Ii=1.5..10x In N conductor protection, opt. w. external current transformer gr.-fault prot., can be sw. off Ig=0.2...1 x In= tg=0.05-0.8s nut keeper kit undervoltage release (UVR) 120-127V AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Initial Value":"50 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"250 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=139141&mlfb=3VA2225-6JQ32-0CL0"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6JQ32-0CL0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is the interrupting capacity of 3VA2225-6JQ32-0CL0 at 415 V?","answer":"At 415 V the interrupting capacity is 187 kA. It also clears 242 kA at 240 V, 187 kA at 440 V, 121 kA at 500 V, and 4.5 kA at 690 V."},{"question":"What is the depth of 3VA2225-6JQ32-0CL0?","answer":"The depth is 86 mm (3.39 in). Width is 105 mm (4.13 in) and height is 181 mm (7.13 in)."},{"question":"Does 3VA2225-6JQ32-0CL0 include an undervoltage release?","answer":"Yes. The breaker is equipped with an undervoltage release (UVR) that trips the breaker when control voltage drops below the dropout threshold."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}