{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6JQ32-0DL0, Molded case circuit breaker, 3-pole, 250 A, 242 kA at 240 V, line protection.","salesMarkdown":"The Siemens SENTRON 3VA2225-6JQ32-0DL0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a full-scale current of 250 A and a maximum interrupting capacity of 2 500 A. Thermal derating is built into the spec: the breaker holds 250 A continuously up to 50 °C ambient, then steps down to 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. ## Integration notes The UVR ensures the breaker drops out on loss of control voltage — useful for safety circuits where a voltage dip must open the main disconnect. Communication function is onboard, so the breaker can report status to a PLC or BMS without an add-on module. ## Selectivity and coordination Its high interrupting capacity (242 kA at 240 V, 187 kA at 415 V, 121 kA at 500 V) gives you headroom for selective coordination with downstream branch breakers — the goal is to clear a fault at the branch without taking the whole panel down. The 375 A minimum trip threshold and 2 500 A maximum setting range let you dial in the pickup for your specific load profile.","metaTitle":"Siemens 3VA2225-6JQ32-0DL0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2225-6JQ32-0DL0 molded case circuit breaker, 250 A rated, 3-pole, 242 kA at 240 V. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"50 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"250 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=122945&mlfb=3VA2225-6JQ32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"The interrupting rating is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. Always match the available fault current at your service voltage."},{"question":"Where can I buy the 3VA2225-6JQ32-0DL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) and a full set of auxiliary switches: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}